NEW! FROM MCI
4-54-SERIES
INDUSTRIAL
CONTROL TRANSFORMERS
CONTROL POWER
TRANSFORMERS
Listed
TUV-EN61558
*3KVA & 5KVA MODLES - UL PENDING

Shown with optional fuse holder bracket
and
optional 100Va & 50Va windings
Primary 208V,
220V,240V,416V,440V,460V,480V
Secondary 80V, 110V,
120V,160V, 220V, 240V
|
MECHANICAL DIMENSIONS |
| Size | L | W | H | ML | MW | MT HOLE |
WGT |
| 250VA | 3.75" | 3.70" | 3.65" | 3.125" | 3.35" | .3" X .575" |
9.50 lbs. |
| 500VA- 650VA | 5.25" | 4.84" | 5.88" | 4.00" | 3.38" | .3" X .575" | 15.04lbs. |
| 750VA-900VA | 5.25" | 5.40" | 5.10" | 4.00" | 4.12" | .3" X .575" |
19.58
lbs. |
| 1KVA-1.15KVA | 6.75" | 5.00" | 5.87" | 5.50" | 3.38" | .3" X .575" | 24.12 lbs. |
| 1.5KVA-1.65KVA | 6.75" | 5.75" | 5.87" | 5.50" | 4.12" | .3" X .575" | 31.44 lbs. |
| 2.KVA-2.15KVA | 6.75" | 7.90" | 6.05" | 5.50" | 5.87" | .315 X .5" | 51.65 lbs. |
| 3KVA-3.15KVA | 9.00" | 10.15" | 7.95" | 7.625" | 6.12" | .315 X .5" | 91.62 lbs |
| 5KVA | 9.00 | 11.15 | 7.95" | 7.625" | 7.12" | .315 X .5" | 106.45lbs |

|
PRIMARY VOLTAGE |
SECONDARY |
OPTIONAL WINDINGS | ||||||||||||||||
|
208V |
220V |
240V |
416V |
440V |
480V |
80V |
110V |
120V |
160V |
220V |
240V |
16V |
24V |
|||||
PART |
VA |
PRIMARY CURRENT IN AMPS |
|
SECONDARY CURRENT IN AMPS |
|
CURRENT IN AMPS | ||||||||||||
|
4-54-0200 |
250 |
1.20 |
1.36 |
1.04 |
.60 |
.57 |
.52 |
|
3.12 |
2.28 |
2.08 |
1.56 |
1.13 |
1.04 |
|
NA |
NA |
|
|
4-54-0500 |
500 |
2.40 |
2.27 |
2.08 |
1.20 |
1.14 |
1.04 |
|
6.25 |
4.55 |
4.17 |
3.13 |
2.27 |
2.08 |
|
|||
|
4-54-0516 |
550 |
2.64 |
2.50 |
2.29 |
1.32 |
1.25 |
1.15 |
|
6.25 |
4.55 |
4.17 |
3.13 |
2.27 |
2.08 |
|
3.13 |
|
|
|
4-54-0524 |
600 |
2.88 |
2.73 |
2.50 |
1.44 |
1.36 |
1.25 |
|
6.25 |
4.55 |
4.17 |
3.13 |
2.27 |
2.08 |
|
|
4.17 |
|
|
4-54-0540 |
650 |
3.13 |
2.95 |
2.71 |
1.56 |
1.48 |
1.35 |
|
6.25 |
4.55 |
4.17 |
3.13 |
2.27 |
2.08 |
|
3.13 |
4.17 |
|
|
4-54-0700 |
750 |
3.61 |
3.41 |
3.13 |
1.80 |
1.70 |
1.56 |
|
9.38 |
6.82 |
6.25 |
4.69 |
3.41 |
3.13 |
|
|
||
|
4-54.0716 |
800 |
3.85 |
3.64 |
3.33 |
1.92 |
1.82 |
1.67 |
|
9.38 |
6.82 |
6.25 |
4.69 |
3.41 |
3.13 |
|
3.13 |
|
|
|
4-54-0724 |
850 |
4.09 |
3.86 |
3.54 |
2.04 |
1.93 |
1.77 |
|
9.38 |
6.82 |
6.25 |
4.69 |
3.41 |
3.13 |
|
|
4.17 |
|
|
4-54-0740 |
900 |
4.33 |
4.09 |
3.75 |
2.16 |
2.05 |
1.88 |
|
9.38 |
6.82 |
6.25 |
4.69 |
3.41 |
3.13 |
|
3.13 |
4.17 |
|
|
4-54-1000 |
1000 |
4.81 |
4.55 |
4.17 |
2.40 |
2.27 |
2.08 |
|
12.50 |
9.09 |
8.33 |
6.25 |
4.55 |
4.17 |
|
|||
|
4-54-1016 |
1050 |
5.05 |
4.77 |
4.38 |
2.52 |
2.39 |
2.19 |
|
12.50 |
9.09 |
8.33 |
6.25 |
4.55 |
4.17 |
|
3.13 |
||
|
4-54-1024 |
1100 |
5.29 |
5.00 |
4.58 |
2.64 |
2.50 |
2.29 |
|
12.50 |
9.09 |
8.33 |
6.25 |
4.55 |
4.17 |
|
|
4.17 |
|
|
4-54-1040 |
1150 |
5.53 |
5.23 |
4.79 |
2.76 |
2.61 |
2.40 |
|
12.50 |
9.09 |
8.33 |
6.25 |
4.55 |
4.17 |
|
3.13 |
4.17 |
|
|
4-54-1500 |
1500 |
7.21 |
6.82 |
6.25 |
3.61 |
3.41 |
3.13 |
|
18.75 |
13.64 |
12.50 |
9.38 |
6.82 |
6.25 |
|
|||
|
4-54-1516 |
1550 |
7.45 |
7.05 |
6.46 |
3.73 |
3.52 |
3.23 |
|
18.75 |
13.64 |
12.50 |
9.38 |
6.82 |
6.25 |
|
3.13 |
|
|
|
4-54-1524 |
1600 |
7.69 |
7.27 |
6.67 |
3.85 |
3.64 |
3.33 |
|
18.75 |
13.64 |
12.50 |
9.38 |
6.82 |
6.25 |
|
|
4.17 |
|
|
4-54-1540 |
1650 |
7.93 |
7.50 |
6.88 |
3.97 |
3.75 |
3.44 |
|
18.75 |
13.64 |
12.50 |
9.38 |
6.82 |
6.25 |
|
3.13 |
4.17 |
|
|
4-54-2000 |
2000 |
9.62 |
9.09 |
8.33 |
4.81 |
4.55 |
4.17 |
|
25.00 |
18.18 |
16.67 |
12.50 |
9.09 |
8.33 |
|
|
|
|
|
4-54-2016 |
2050 |
9.86 |
9.32 |
8.54 |
4.93 |
4.66 |
4.27 |
|
25.00 |
18.18 |
16.67 |
12.50 |
9.09 |
8.33 |
|
3.13 |
|
|
|
4-54-2024 |
2100 |
10.10 |
9.55 |
8.75 |
5.05 |
4.77 |
4.38 |
|
25.00 |
18.18 |
16.67 |
12.50 |
9.09 |
8.33 |
|
|
4.17 |
|
|
4-54-2040 |
2150 |
10.34 |
9.77 |
8.96 |
5.17 |
4.89 |
4.48 |
|
25.00 |
18.18 |
16.67 |
12.50 |
9.09 |
8.33 |
|
3.13 |
4.17 |
|
|
*4-54-3000 |
3000 |
14.42 |
13.64 |
12.5 |
7.21 |
6.82 |
6.25 |
|
37.50 |
27.27 |
25.00 |
18.75 |
13.63 |
12.50 |
|
|||
|
*4-54-3016 |
3050 |
14.66 |
13.86 |
12.7 |
7.33 |
6.93 |
6.35 |
|
37.50 |
27.27 |
25.00 |
18.75 |
13.63 |
12.50 |
3.13 | |||
|
*4-54-3024 |
3100 |
14.90 |
14.10 |
12.9 |
7.45 |
7.05 |
6.46 |
|
37.50 |
27.27 |
25.00 |
18.75 |
13.63 |
12.50 |
4.17 | |||
|
*4-54-3040 |
3150 |
15.14 |
14.32 |
13.12 |
7.57 |
7.15 |
6.56 |
|
37.50 |
27.27 |
25.00 |
18.75 |
13.63 |
12.50 |
3.13 | 4.17 | ||
|
*4-54-5000 |
5000 |
24.00 |
22.72 |
20.83 |
12.02 |
11.36 |
10.41 |
|
62.50 |
45.45 |
41.66 |
31.25 |
22.72 |
20.80 |
||||
|
*4-54-5016 |
5000 |
24.00 |
22.72 |
20.83 |
12.02 |
11.36 |
10.41 |
|
61.87 |
45.00 |
41.25 |
30.94 |
22.50 |
20.62 |
3.13 | |||
|
*4-54-5024 |
5000 |
24.00 |
22.72 |
20.83 |
12.02 |
11.36 |
10.41 |
|
61.25 |
44.55 |
40.83 |
30.62 |
22.27 |
20.41 |
4.17 | |||
|
*4-54-5040 |
5000 |
24.00 |
22.72 |
20.83 |
12.02 |
11.36 |
10.41 |
60.62 |
44.10 |
40.42 |
30.31 |
20.04 |
20.21 |
3.13 | 4.17 | |||
CAUTION-----INSTALLATION AND CONNECTIONS SHOULD BE DONE BY QUALIFIED ELECTRICIAN OR ENGINEER ONLY.
LOCAL ELECTRICAL CODES/REGULATIONS MUST BE OBSERVED.
DANGER OF FIRE OR ELECTRICAL SHOCK COULD RESULT FROM INCORRECT INSTALLATION OR CONNECTIONS.
MCI 4-54 transformers are designed to accommodate a wide range of input and output voltage combinations or to compensate for various high line or low line applications.
Below is a list of various connections for different voltages. It is also possible to accommodate other voltages by using combinations of input and output jumpers. . Feel free to contact factory to configure connections for special requirements. Be sure to measure output voltages before connecting load. Remember no-load output voltage will be around 5% greater than voltage out when load is applied.
INPUT VOLT JUMPER INPUT ON
480V H4 TO H5 H1 & H8
460V H4 TO H5 H1 & H7
450V H4 TO H5 H1 & H6
440V H3 TO H5 H1 & H7
430V H3 TO H5 H1 & H6
420V H2 TO H5 H1 & H6
240V H1 TO H5 & H4 TO H8 H1 & H8
230V same as 240V but take output off
higher secondary output connection.
220V H1 TO H5 & H3 TO H7 H1 & H7
208V H1 TO H5 & H2 TO H6 H1 & H6
200V SAME AS 220V, OUTPUT ON 110V CONNECTION
OUTPUT VOLT JUMPER OUTPUT ON
240V X4 TO X5 X1 TO X8
230V X3 TO X5 X1 TO X8
220V X3 TO X5 X1 TO X7
208V same as 220V but input on 5%
voltage up connection from actual input voltage.
Example; input 440V to 460V connection.
120V X1 TO X5 & X4 TO X8 X1 TO X8
115V same as 120V but input on 5% higher
Voltage up connection from actual input voltage.
110V X1 TO X5 & X3 TO X7 X1 TO X7
100V same as 110v but input on 10% higher voltage
Up input connection.
MCI TRANSFORMER
CORPORATION
411 Manhattan Avenue, Babylon,
NY 11704 • 631. 587. 0510 • FAX: 631. 587. 0624
25
Blodgett Street, Orange, MA 01364 • 978. 544. 8272 • FAX: 978. 544. 8356
150 Sanhedrin, Willits, CA 95490 • 707. 459. 5994 • FAX:
707. 459. 5998
Email us your questions at info@mcitransformer.com
Sales Reps:
Texas &
Oklahoma • Brady Waters Co.
www.bradywaters.com
PHONE
866. 463. 5900
214. 545.
6200